Mitigation of Lower Order Harmonics in a Grid- Connected Single-Phase PV Inverter
Prakash Solanki, Ripan Patel
PG student, LCIT, Bhandu and 384120, India, India
Abstract
In this paper, among from the all topologies ordinary single-phase PV inverter topology considered which is grid-connected, also single-phase inverter with an inductive filter, and a step-up transformer interfacing is considered. Generally, this configuration will not introduce any lower order harmonics into the grid due to highfrequency PWM operation. However, an Unconventional factors in the system like core saturation-induced distorted magnetizing current of the transformer and the dead time of the inverter, etc., participate to a significant amount of lower order harmonics in the grid current. A proposed system of inverter current control that reduced lower order harmonics is observed in this paper. An adaptive technique is used for the lower order harmonic compensation. Furthermore, a proportional-resonant-integral (PRI) controller and its design are also presented. This controller removes the dc component in the control system, which inject even harmonics in the grid current in the topology considered. The complete design has been validated with Simulation results.
Keywords
How to cite
Prakash Solanki, Ripan Patel (2016). Mitigation of Lower Order Harmonics in a Grid- Connected Single-Phase PV Inverter. IJAREST, 3(5), 65-74.
BibTeX
@article{ijarest2016C6AB95,
title={{Mitigation of Lower Order Harmonics in a Grid- Connected Single-Phase PV Inverter}},
author={Prakash Solanki and Ripan Patel},
journal={IJAREST},
volume={3},
number={5},
pages={65-74},
year={2016}
}Published under an open-access licence. See copyright & licensing.